MEGATEC(8)
NAME
megatec - Driver for Megatec protocol based UPS equipment
NOTE
This  man  page  only  documents  the hardware-specific features of the
megatec driver. For information about  the  core  driver,  see  nutupsdrv(8).
SUPPORTED HARDWARE
The  megatec  driver  is  known to work with various UPSes from Blazer,
Energy Sistem, Fenton Technologies, Mustek and  many  others.  The  NUT
compatibility table lists all the known supported models. Keep in mind,
however, that other models not listed there may also be  supported  but
haven't been tested.
On  models  with  both a serial port (RS-232) and an USB port, only the
serial port is supported. Connecting a computer which does not  have  a
serial interface to the UPS serial port using a USB-to-serial converter
should work, provided the converter is supported by your operating system.
EXTRA ARGUMENTS
This driver supports some extra parameters (see ups.conf(5)):
- mfr=string
- Optional. Specify the UPS manufacturer name.
- model=string
 Optional. Specify the UPS model name.
- serial=string
 Optional. Specify the UPS serial number.
- offdelay=int
 Optional. After receiving a shutdown command, the UPS will wait this many minutes before turning off the load. Specify this if the UPS must remain online for a short period of time after the computer has powered down. The default is 0 (turn off immediately).
- ondelay=int
 Optional. After turning off the load (see offdelay), the UPS will wait at least this many minutes before coming back online. If line power gets restored before this delay expires, the UPS will wait until it does. If line power gets restored after this delay expires, the UPS will power on the load immediately. The default is 2 minutes.
- lowbatt=float
 Optional. Low battery level (%). Overrides the hardware default level. Cannot be used if the driver is unable to calculate the charge percentage for your UPS automatically (see KNOWN PROBLEMS) and the battvolts parameter isn't specified.
- battvolts=float:float
 Optional. The battery voltage interval (see KNOWN PROBLEMS).
- battvoltmult=num
 Optional. Multiply the reported battery voltage by this number. Some devices report only a fraction of the total battery voltage. The default is 1.
- dtr=int
 Optional. Some UPS models need the DTR serial line set to a specific state, either 0 or 1. See also rts.
- rts=int
 Optional. Some UPS models need the RTS serial line set to a specific state, either 0 or 1. See also dtr.
- ignoreoff
 Optional. This option should be used if upsc(8) shows the UPS status as OFF when it's clearly on. This will force the driver to ignore the OFF status altogether.
- sendpace=int
 Optional. This option can be used to change the wait interval between each character that is sent to the UPS, between 1 and 1000 milliseconds. Some models may need this if the default interval (100 milliseconds) proves to be too long, or too short.
UPS COMMANDS
This driver supports some instant commands (see upscmd(8)):
- beeper.toggle
- Toggle the UPS beeper. (Not available on some hardware.)
- load.on
- Turn on the load immediately.
- load.off
- Turn off the load immediately (see KNOWN PROBLEMS).
- reset.input.minmax
- Reset minimum and maximum input voltage status.
- reset.watchdog
- Restarts the UPS watchdog timeout. The watchdog is started if it isn't running, which means the UPS shuts down one minute after this command is executed for the last time, restarting one minute afterwards. To cancel the watchdog, run the "shutdown.stop" command.
- shutdown.return
- Turn off the load and return when power is back. Uses the timers defined by ondelay and offdelay.
- shutdown.stayoff
- Turn off the load and remain off (see KNOWN PROBLEMS). Uses the timer defined by offdelay.
- shutdown.stop
- Stop a shutdown in progress.
- test.battery.start.deep
- Perform a long battery test (Not available on some hardware.)
- test.battery.start
- Perform a (10 second) battery test.
- test.battery.stop
- Stop a running battery test. (Not available on some hardware.)
KNOWN PROBLEMS
The battery charge (%) value is only a best-effort calculation and  may
be  incorrect,  or  non-existant, for some UPS models. In any case, you
can always resort to finding the voltages at which the battery  becomes
fully discharged and fully charged, and specify them manually using the
"battvolts" option.  If you do this, please notify the author  of  this
driver so that information can be added to the NUT hardware compatibility list. Note that if you also specified  the  "battvoltmult"  option,
you  need  to  divide the found voltages for fully discharged and fully
charged by this number.
Some UPS commands aren't supported by all models. In  most  cases,  the
driver  will  send  a  message to the system log when the user tries to
execute an unsupported command. Unfortunately, some models  don't  even
provide a way for the driver to check for this, so the unsupported commands will silently fail.
Both the "load.off" and "shutdown.stayoff" instant commands  are  meant
to turn the load off indefinitely. However, some UPS models don't allow
this.  When this is the case, the driver will tell the UPS to turn  off
the  load for 9999 minutes (about 7 days) and a message will be sent to
the system log.
Some models report a bogus value for the beeper status (will always  be
"enabled" or "disabled"). So, the "beeper.toggle" command may appear to
have no effect in the status reported by the driver when, in  fact,  it
is working fine.
The temperature value is also known to be bogus in some models.
AUTHOR
Carlos Rodrigues <carlos.efr at mail.telepac.pt>
SEE ALSO
- nutupsdrv(8), upsc(8), upscmd(8), upsrw(8)
- Internet resources:
- The NUT (Network UPS Tools) home page: http://www.networkupstools.org/