NAME
powerpanel - Driver for PowerPanel Plus compatible UPS equipment
NOTE
This man page only documents the hardware-specific features of the powerpanel driver.  For information about the  core  driver,  see  nutupsdrv(8).
SUPPORTED HARDWARE
This  driver  supports CyberPower BC1200, PR2200 and many other similar
devices, both for the  text  and  binary  protocols.  The  driver  will
autodetect which protocol is used.
EXTRA ARGUMENTS
This driver supports the following optional settings in ups.conf(5):
- protocol=[text,binary]
- Override the default autodetection of the protocol.
- manufacturer=value
- If you don't like the autodetected value, you can override this by setting it here.
- model=value
- Like manufacturer above.
- serial=value
- Like manufacturer above.
- ondelay=value
- Time to wait before switching on the UPS (1 - 9999 minutes, 0 indefinite). Only available with the text protocol driver (see SUPPORT STATUS).
- offdelay=value
- Time to wait before shutting down the UPS (6 - 600 seconds). Values below 60 seconds will be truncated to 6 seconds intervals, values above 60 seconds to 60 seconds intervals. Only available with the text protocol driver (see SUPPORT STATUS).
VARIABLES
Depending on the type of your UPS unit, some of the following variables
may be changed. If the driver can't read a variable from  the  UPS,  it
will not be made available.
- input.transfer.high
- writable: high transfer voltage point in V
- input.transfer.low
- writable: low transfer voltage point in V
- battery.charge.low
- writable: remaining battery charge percentage for low battery warning
- output.voltage.nominal
- writable: nominal output voltage in V
- ups.start.battery
- writable: allow cold start from battery
COMMANDS
Depending on the type of your UPS unit, some of the following  commands
may be available.
test.battery.start.quick, test.battery.stop
beeper.enable, beeper.disable, beeper.toggle
- shutdown.return, shutdown.reboot, shutdown.stayoff
- On many devices, these commands are unreliable, so before using them you must verify that these work as expected (see SHUTDOWN ISSUES).
- shutdown.stop
SUPPORT STATUS
Vendor  support is absent for this driver, so if you need some features
that are currently not available, provide ample documentation  on  what
the  driver  should sent to the UPS in order to make this work. If more
information would be available on the binary protocol, it would  probably  be  possible  to  make  ondelay and offdelay configurable. So far,
nobody has taken the time to investigate what we should tell the UPS to
make this work and CyberPower isn't willing to share this with us.
SHUTDOWN ISSUES
If  the  shutdown.return  command  on  your  UPS  doesn't seem to work,
chances are that your UPS is of an older model. Try a couple of different  settings for offdelay. If no value in the range 6..600 works, your
UPS likely doesn't support this. In order to get  the  expected  behaviour,   it  requires  shutdown.stayoff  (when  on  battery)  and  shutdown.reboot (when on mains). The driver will automatically fallback  to
these  commands  if shutdown.return fails and tries to detect which one
should be used when called with the '-k' option (or  through  upsdrvctl
shutdown).
This  isn't  bullet  proof  however and you should be prepared that the
power will either not be shutdown or that it doesn't  return  when  the
power  comes back. All models supported by the binary protocol and many
supported through the text protocol are affected by this.
KNOWN PROBLEMS
The CyberPower OP series don't offer direct voltage, charge,  frequency
and temperature readings. Instead, they will return a binary value that
needs conversion to the actual value.
The exact conversion needed is unknown at the  time  of  this  writing,
hence  an  estimation  was  made based om readings from actual devices.
This may (probably will) be off, possibly a lot. Unless you can tell us
the  exact  mapping  between  values  from the UPS and actual readings,
don't bother to complain. We've done the best we can based on the  limited  information  available. Remember, a UPS isn't a measuring instrument.
AUTHORS
Arjen de Korte <arjen@de-korte.org>, Doug Reynolds <mav@wastegate.net>